The elevation must not be above 2000m
Surrounding medium temperature limit to + 40 ℃, the lower limit of 25 ℃;
Installation site of air relative humidity when the highest temperature is + 40 ℃ not more than 50%, at a lower temperature can have higher relative humidity, such as 20 ℃ at 90%.Due to temperature change occasionally produce condensation special measures should be taken
Model | Nominal discharge current In(8/20μs)kA | Maximum continuous operating voltage Uc V~ | Voltage protection level Up kV | Impulse currentIimp(10/350μs)kA | Charge Q As | Response time ns | Combination mode | Unipolar width mm | Backup fuse |
HSU8-I15 | 50 | 385 | 2.5 | 15 | 7.5 | ≤25 | 1P~4P | 36 | 125 |
Model | Nominal discharge current In(8/20μs)kA | Maximum continuous operating voltage Uc V~ | Voltage protection level Up kV | Maximum discharge current Imax(8/20μs)kA | Response time ns | Combination mode | Unipolar width mm | Backup fuse |
HSU8-15 |
5 |
275 | 1.2 |
15 |
≤25 |
1P~4P |
18 |
16 |
385 | 1.8 | |||||||
460 | 2.0 | |||||||
HSU8-40 |
15 |
275 | 1.2 |
40 |
32 |
|||
385 | 1.8 | |||||||
460 | 2.0 | |||||||
HSU8-60 | 25 | 385 | 1.8 | 60 | 63 | |||
460 | 2.0 | |||||||
HSU8-100 | 40 | 385 | 2.2 | 100 |
36 |
80 | ||
460 | 2.5 | |||||||
HSU8-120 | 50 | 460 | 3.5 | 120 | 100 | |||
HSU8-150 | 60 | 460 | 3.5 | 150 | 125 |