The series circuit breakers possesses seven rated frames: 63A、100A、250A、400A、630A、800A, current specification 10 A ~ 800 A.
- limited short circuit breaking capacity can be divided into L type (Typical), M type (High breaking type);
- All series circuit breaker can be installed horizontally (lateral), vertical (vertical) and horizontal installation;
- Whole series of breaker with isolation function
- The circuit breaker can be configured with a transparent cover, which can observe the Splitting or Integrating state of moving and stationery contact-header.
- The breaker can be divided into Electricity and motor protection by purpose.
Working conditions
The surrounding medium temperature ranging from -5℃ to +40℃, average value within 24 hours not over +35℃.
Altitude not exceeding 2000 meters above sea level.
Relative humidity of installation site not over 50% at an ambient temperature of +40℃ yet higher humidity is permissible at lower temperature, e.g. 90% at 20℃, Particular measures should be taken for occasional condensation due to temperature fluctuation.
Pollution grade: 3
The MCCB should be installed in places where there is no potential explosion risk nor electric conducting dust, nor metal corrosion and insulation damage situations.
The MCCB should be installed in places where there is no rain and snow.
Type | HSM2-63 | HSM2-100 | HSM2-250 | HSM2-400 | HSM2-630 | HSM2-800 | |||||||
Breaking grade | L | M | L | M | L | M | L | M | L | M | L | M | |
Rated current A | 10/16/20/25/32/
40/50/63 |
16/20/25/32/40/50/63/
80/100/125 |
16/20/32/40/50/63/80/100 | 225/250/315/350/400 | 400/500/630 | 630/700/800 | |||||||
Pole number | 2/3/4 | ||||||||||||
Rated insulation voltage V | 800 | ||||||||||||
Rated impulse withstand voltage V | 8000 | ||||||||||||
Rated voltage | 400、690 | ||||||||||||
Flashover distance | <50 | ||||||||||||
Rated limited short circuit breaking capacity kA | AC400V | 25 | 50 | 35 | 50 | 35 | 50 | 50 | 65 | 50 | 65 | 65 | 70 |
Rated service short circuit breaking capacity kA | AC400V | 18 | 35 | 22 | 30 | 22 | 30 | 30 | 50 | 35 | 50 | 45 | 65 |
Operating performance(life) times | load | 8000 | 8000 | 8000 | 8000 | 7500 | 7500 | ||||||
Without load | 20000 | 20000 | 20000 | 20000 | 10000 | 10000 | |||||||
boundary dimension(Wide* high*deep) | two-pole | / | 65×150×68(86) | 75×165×86(103) | / | / | |||||||
three-pole | 78×135×74(82) | 92×150×68(86) | 107×165×86(103) | 150×257×108 | 182×270×110 | 210×280×115.5 | |||||||
four-pole | 100×135×74(82) | 122×150×68(86) | 142×165×86(103) | 184×257×108 | 240×270×110 | 280×280×115.5 |