The series circuit breakers possesses seven rated frames: 63A、125A、250A、400A、630A、800A, the current specification 12.5 A ~ 800 A.
- limited short circuit breaking capacity can be divided into E type (Economical), S type (Typical), M type (Middle and high breaking type), H type (High breaking type), L type (current limiting type);
- All series circuit breaker can be installed horizontally (lateral), vertical (vertical) and horizontal installation;
- Whole series of breaker with isolation function
- The circuit breaker meet the use requirements of installation site with the altitude not exceeding 4000 meters above sea level (need correcting when the altitude above 2000 meters).
- The outlet and inlet of circuit breaker with protective cover
- The breaker can be divided into Electricity and motor protection by purpose.
- Working conditions
The surrounding medium temperature ranging from -5℃ to +40℃, average value within 24 hours not over +35℃.
Altitude not exceeding 4000 meters above sea level (need correcting when the altitude above 2000 meters).
Relative humidity of installation site not over 50% at an ambient temperature of +40℃ yet higher humidity is permissible at lower temperature, e.g. 90% at 20℃(humid type circuit breaker at 25℃ is 95%), Particular measures should be taken for occasional condensation due to temperature fluctuation.
Pollution grade: 3
Ⅲ for primary circuit of MCCB and coils of undervoltage releases and Ⅱ for auxiliary circuits and control circuits.
Humid type circuit breaker can affected by damp and hot, salt fog, fog bacteria.
The MCCB should be installed in places where there is no potential explosion risk nor electric conducting dust, nor metal corrosion and insulation damage situations.
The MCCB should be installed in places where there is no rain and snow.
Type | HSM1-63 | HSM1-125 | HSM1-160 | HSM1-250 | HSM1-400 | HSM1-630 | HSM1-800 | ||||||||||||||||||||||
Breaking grade | S | H | E | S | M | H | E | S | H | L | S | M | H | L | S | M | H | L | S | M | H | S | M | H | |||||
Rated current A | 10/12.5/16/20/32/40/50/63 | 12.5/16/20/25/32/40/50/63/80/100/125 | 16/20/32/40/50/63/80/100/125/160 | 100/125/160/180/200/225/250 | 200/225/250/315/350/400 | 400/500/630 | 500/630/700/800 | ||||||||||||||||||||||
Pole number | 3/4 | ||||||||||||||||||||||||||||
Rated insulation voltage V | 800 | ||||||||||||||||||||||||||||
Rated impulse withstand voltage V | 8000 | ||||||||||||||||||||||||||||
Rated voltage | 400、690 | ||||||||||||||||||||||||||||
Flashover distance | 0 | <30 | <50 | 0 | <50 | 0 | |||||||||||||||||||||||
Rated limited short circuit breaking capacity kA | AC400V | 25 | 35 | 15 | 25 | 35 | 50 | 25 | 35 | 50 | 80 | 35 | 50 | 65 | 85 | 35 | 50 | 65 | 85 | 50 | 65 | 80 | 50 | 65 | 80 | ||||
AC690V | / | / | / | / | / | 20 | / | / | 20 | / | / | / | 20 | / | / | / | 20 | / | / | / | 20 | / | / | 30 | |||||
Rated service short circuit breaking capacity kA | AC400V | 25 | 35 | 7 | 16 | 25 | 50 | 25 | 18 | 42 | 50 | 18 | 30 | 48 | 60 | 18 | 30 | 48 | 60 | 30 | 48 | 60 | 30 | 48 | 60 | ||||
AC690V | / | / | 10 | / | / | 10 | / | / | / | 10 | / | / | / | 10 | / | / | / | 10 | / | / | 20 | ||||||||
Operating performance(life) times | load | 8000 | 8000 | 8000 | 8000 | 7000 | 7000 | 7000 | |||||||||||||||||||||
Without load | 20000 | 20000 | 20000 | 20000 | 10000 | 10000 | 10000 | ||||||||||||||||||||||
boundary dimension(Wide* high*deep) | three-pole | 72×120×70 | 76×120×70(80) | 90×120×70(80) | 105×170×103.5 | 140×254×103.5 | 210×268×103.5 | 210×268×103.5 | |||||||||||||||||||||
four-pole | 95×120×70 | 101×120×70(80) | 120×120×70(80) | 140×170×103.5 | 184×254×103.5 | 280×268×103.5 | 280×268×103.5 |