Installation site altitude not exceeding 2000m
The upper limit of ambient temperature is +55 DEG C, the lower limit is -25
The air relative humidity at the installation site shall be no more than 50% at the maximum temperature of +40 degrees celsius and can have a higher relative humidity at a lower temperature,for example air relative humidity can reach up to 90% under 20 degrees celsius.Special measures should be taken when changing temperature produces condensation.
Installation site pollution level of 3
The main circuit of the installation class is III, and the rest of the control and auxiliary circuits are Ⅱ
Installation method : Vertical installation, Inclination of the mounting surface ≤±22.5°
Table 1
Model | HSC1-6.3 | HSC1-9M | HSC1-9 | HSC1-12 | HSC1-16 | HSC1-25 | HSC1-32 | HSC1-40 | |||
Rated insulation voltage Ui V | 690 | ||||||||||
Rated heating Current Ith A | 16 | 20 | 30 | 45 | |||||||
Rated working Voltage Ue V | 230 400 690 | ||||||||||
Rated working current Ie A |
AC-3 |
230V | 6.3 | 9 | 9 | 12 | 16 | 25 | 32 | 40 | |
400V | 6.3 | 9 | 9 | 12 | 16 | 25 | 32 | 40 | |||
690V | 3.5 | 6.9 | 6.9 | 9.1 | 12.5 | 12.5 | 22.1 | 22.1 | |||
AC-4 |
230V | 5 | 6.3 | 6.3 | 9 | 12 | 16 | 25 | 32 | ||
400V | 5 | 6.3 | 6.3 | 9 | 12 | 16 | 25 | 32 | |||
690V | 2.8 | 5 | 5 | 6.7 | 8.9 | 8.9 | 17.8 | 17.8 | |||
Control motor power
Kw AC-3 |
230V | 1.7 | 2.2 | 2.2 | 3.0 | 4.0 | 6.1 | 8.5 | 11 | ||
400V | 3.0 | 4.0 | 4.0 | 5.5 | 7.5 | 11 | 15 | 18.5 | |||
690V | 3.0 | 5.5 | 5.5 | 7.5 | 11 | 11 | 18.5 | 18.5 | |||
mechanical endurance Million times | 1000 | ||||||||||
Long-life electrical AC-3
Million times AC-4 |
100
5 |
||||||||||
Million times AC-3
次/h AC-4 No load |
800
250 7000 |
||||||||||
Operating |
Rated voltage Us | 36V 110V 127V 230V 400V | |||||||||
Start power consumption VA | 32 | 70 | 102 | 120 | |||||||
Holding power consumption VA | 5 | 8 | 12 | 15 | |||||||
Energy efficiency grade | 3 | 3 | 3 | 3 | |||||||
Top mounted auxiliary contact |
Model Form
CA122 2NO2NC CA131 3NO1NC CA140 4NO |
Model Form
CA222 2NO2NC CA231 3NO1NC CA240 4NO |
|||||||||
Side mounted auxiliary contact | – | Model:CA411
Form:1NO1NC |
|||||||||
Delay module (Top mounting) |
Delay on |
– |
Model:TE1-3 TE1-30 TE1-180
Delay range:0.1~3s 1~30s 10~180s |
||||||||
Delay off | Model:TE2-3 TE2-30 TE2-180Delay range
Delay range:0.1~3s 1~30s 10~180s |
||||||||||
Communication interface module | – | ||||||||||
Surge suppression module | – | ||||||||||
Surge suppression module | – | ML1 |
continued Table 1
Model | HSC1-50 | HSC1-63 | HSC1-75 | HSC1-95 | HSC1-110 | HSC1-140 | HSC1-170 | HSC1-205 | |||||
Rated insulation voltage Ui V | 690 | ||||||||||||
Rated heating current Ith A | 70 | 95 | 140 | 205 | |||||||||
Rated heating current Ith A | 230 400 690 | ||||||||||||
Rated working current Ie A |
AC-3 |
230V | 50 | 63 | 75 | 95 | 110 | 140 | 170 | 205 | |||
400V | 50 | 63 | 75 | 95 | 110 | 140 | 170 | 205 | |||||
690V | 34.6 | 34.6 | 61 | 61 | 110 | 118 | 170 | 170 | |||||
AC-4 |
230V | 40 | 50 | 63 | 75 | 90 | 110 | 140 | 170 | ||||
400V | 40 | 50 | 63 | 75 | 90 | 110 | 140 | 170 | |||||
690V | 25 | 25 | 52.8 | 52.8 | 60 | 95 | 100 | 122 | |||||
Control motor
Power Kw AC-3 |
230V | 15 | 18.5 | 22 | 22 | 37 | 45 | 55 | 64 | ||||
400V | 22 | 30 | 37 | 45 | 55 | 75 | 90 | 110 | |||||
690V | 30 | 30 | 55 | 55 | 75 | 110 | 156 | 156 | |||||
mechanical endurance Million times | 1000 | ||||||||||||
mechanical endurance Million times AC-3
Million times AC-4 |
100
5 |
||||||||||||
Million times AC-3 times/h AC-4
No load |
800
250 7000 |
800
250 5000 |
750
250 5000 |
700
200 5000 |
500
130 5000 |
||||||||
Operating coil |
Rated voltage Us | 36V 110V 127V 230V 400V | |||||||||||
Start power consumption VA | 190 | 275 | 387 | 906 | |||||||||
Holding power consumption VA | 20.5 | 30 | 33 | 4.0 | |||||||||
Energy efficiency grade | 2 | 2 | 2 | 2 | |||||||||
Top mounted auxiliary contact |
Model Form
CA322 2NO2NC CA331 3NO1NC CA340 4NO |
– |
|||||||||||
Side mounted auxiliary contact | Model:CA511 CA520 CA502 Form:1NO1NC 2NO 2NC | ||||||||||||
Delay module (Top mounting ) |
Delay on |
– |
Model:TE1-3 TE1-30 TE1-180
Delay range:0.1~3s 1~30s 10~180s |
– |
|||||||||
Delay off | Model:TE2-3 TE2-30 TE2-180
Delay range:0.1~3s 1~30s 10~180s |
||||||||||||
Communication interface module | TX1 | ||||||||||||
Surge suppression module | RC1 | ||||||||||||
Mechanical locking module | ML1 | – |
continued Table 1
Model | HSC1-250 | HSC1-300 | HSC1-400 | HSC1-475 | HSC1-630 | HSC1-800 | |||||
Rated insulation voltage Ui V | 690 | ||||||||||
Rated heating current Ith A | 300 | 400 | 475 | 630 | 800 | ||||||
Rated working voltage Ue V | 230 400 690 | ||||||||||
Rated working current Ie A |
AC-3 |
230V | 250 | 300 | 400 | 475 | 630 | 800 | |||
400V | 250 | 300 | 400 | 475 | 630 | 800 | |||||
690V | 205 | 250 | 300 | 400 | 630 | 800 | |||||
AC-4 |
230V | 205 | 250 | 300 | 300 | 570 | 570 | ||||
400V | 205 | 250 | 300 | 270 | 520 | 520 | |||||
690V | 160 | 160 | 190 | 190 | 362 | 362 | |||||
Control motor
power Kw AC-3 |
230V | 78 | 93 | 125 | 145 | 191 | 250 | ||||
400V | 132 | 160 | 200 | 250 | 335 | 450 | |||||
690V | 190 | 235 | 275 | 375 | 573 | 750 | |||||
mechanical endurance Million times | 600 | ||||||||||
Long-life electrical AC-3
Million times AC-4 |
60
5 |
||||||||||
Operating frequency AC-3
次/h AC-4 No load |
700
200 3000 |
500
130 3000 |
500
150 2000 |
400
150 2000 |
500
150 1000 |
||||||
Operating coil |
Million times Us | 36V 110V 127V 230V 400V | |||||||||
Start power consumption
VA |
906 | 620 | 1018 | ||||||||
Holding
power consumption VA |
4.0 | 11 | 14 | ||||||||
Energy efficiency grade | 2 | 2 | 2 | – | |||||||
Top mounted auxiliary contact | – | ||||||||||
Side mounted auxiliary contact | Model:CA511 CA520 CA502 Form:1NO1NC 2NO 2NC | ||||||||||
Delay module (Top mounting) |
Delay on |
– |
|||||||||
Delay off | |||||||||||
Communication interface module | TX1 | ||||||||||
Surge suppression module | RC1 | ||||||||||
Mechanical locking module | – |
notes:
- HSC1-6.3 ~ 12 also can provide the four poles
- Mechanical locking module does not separate supply and must be matched with the contactor. When not specified, auxiliary contacts with 1 open and 1 closed
- GB21518 suitable 《 AC contactor energy efficiency limit value and energy efficiency grade 》 for rated operating current 6A ~ 630A AC contactor
- The reversible AC contactor has the same parameters as the standard
Table 2
Table 2 | HSC1-25C | HSC1-40C | HSC1-63C | HSC1-95C | |
Rated insulation voltage Ui | 690V | ||||
Rated heating current Ith | 30A | 45A | 70A | 95A | |
Rated working voltage Ue | 230V 400V | ||||
Rated working current Ie | 230V | 25 | 40 | 63 | 95 |
400V | 25 | 40 | 63 | 95 | |
AC-6b
Rated control capacity kvar |
230V | 10 | 15 | 25 | 35 |
400V | 15 | 30 | 45 | 60 | |
Surge suppression capability | ≤20Ie | ||||
mechanical endurance Million times | 100 | ||||
AC-6b Long-life electrical Million times | 10 | ||||
Operating frequency times/h | 240 | 120 | |||
Operating coil characteristics and power consumption | AC contactor with HSC1 serie | ||||
Auxiliary contact ( Side loading ) |
Factory configuration:CA411 1只
Optional installation :CA411 1只
|
Factory configuration:CA511 1只
Optional installation :CA511 or CA52 or CA502 1只 |
|||
Equipped with a fuse model | RT16-50 | RT16-63 | RT16-125 | RT16-160 |