The elevation must not be above 2000m
Surrounding medium temperature limit to + 40 ℃, the lower limit of 25 ℃;
Installation site of air relative humidity when the highest temperature is + 40 ℃ not more than 50%, at a lower temperature can have higher relative humidity, such as 20 ℃ at 90%.Due to temperature change occasionally produce condensation special measures should be taken
Installation site pollution level 2;
Installation category main circuit for Ⅲ;
Installation method: vertical installation;
No significant vibration and shock
Product model | Pole | Rated voltage Ue V | Rated current In A | Rated residual operating current IΔn mA | Breaking capacity Icu/Ics kA | The instantaneous tripping type |
HSM9L-125 | 1+N,2 | 230 | 50、63、80、100、125 | 30/100/300 | 10/7.5 | C型:8In±20%;
D型:12In±20% |
3,3+N,4 | 400 | |||||
HSM9L-63 | 1+N,2 | 230 | 6、10、16、20、25、32、40、50、63 | 10/7.5 | C、D | |
3,3+N,4 | 400 | |||||
HSM9L-63M | 1+N,2 | 230 | 6 | |||
3,3+N,4 | 400 | |||||
HSM9NL-40 | 1+N | 230 | 6、10、16、20、25、32 | 10/30 | 10/7.5 | |
HSM9NL-40M | 6 |